There are 3 primary control logic modes:
·'Drainage'where control is concentrated at the source 'Bosting'which references pressure switching on the delivery side for control 'Transfer'which is a mix of source and destination control
The LCD screen displays the pump running state and provides the user a wealth of useful information.
The controller is easy to set up with an initial push button calibration and individual parameters can be fine-tuned.
This controller is particularly useful where there is the need to control and protect pump installations managing the automatic operation through a variety of switching methods without the need to create a bespoke control solution.
Control panel applications:

On the main PCB there is a2 position 'Dip Switch'
To alter the control logic to suit an application,the installer must select the appropriate switch position.
After selecting the desired switch position,cycle the controller power to apply the setting.
| Switch position | Control logic -Applications | |
| 1 | 11 | 'Pressure Boosting'Mode.Main control via(N/C)pressure switch.Supports run/no run level protection at the source via floats or probes. |
| 2 | 01 | 'Drainage'Mode where the control inputs(generally level floats or probes)are located at the source. |
| 3 | 00 | 'Transfer'Mode.Main control via control inputs (floats or probes)at destination or by a pressure switch on the delivery line.Supports run/no run level protection at the source. |
| 4 | 10 | Sensorless time control |
TECHNICAL SPECIFICATON
| Controller Modes | Automatic or Manual operation. Liquid level control via float switch or electrode probes. Pressure control via pressure switch. |
|
| Protection functions: Dry run (Underload),Overload,Pump Stalled, Open and reverse phase,Under voltage,Over voltage, Short circuit,Pump Maximum run time | ||
| Input Voltage | Single Phase:230V+10%-6% Three Phase: 415V+10%-6% |
|
| Rated output power | 0.37 to 2.2 kW P2 power (max 15A input) 0.37 to 4 kW P2 power (max 12A input) 2.2 to 7.5 kW P2 power(max 18A input) |
|
| Minimum Amperage | 1.0 amp to achieve calibration successfully(5 amp for 3-7.5) | |
| Working temp | -25 to+55 deg C 20%to 90%relative humidity,non-condensing |
|
| Controller size | 200mm wide,275mm tall,125 deep. IP54 | |
| Trip response times (set) | Open phase-Less than 2 sec Short circuit-less than 0.1 sec |
|
| Trip Voltage (User adjustable) |
Over voltage Default =265V Default =460V Under voltage Default =196V Default =340V |
|
| Trip response times (User adjustable) |
Dry run (Under-load) Under Voltage Over voltage |
3 sec Less than 5 sec Less than 5 sec |
| Recovery times (User adjustable) |
Dry run (Under-load) 30 min default Overload 30 min default Under Voltage 5 min default Over voltage 5 min default |
|
| Alarms | Audible alarm and flashing screen.Does not support auxiliary alarm | |
Displaying
This controller display provides a real time indication of the operational mode and the current state of the controller,including real-time voltage/current and any error messages.
Only the icons relevant to the selected operational mode will display.

Parameter setting
|
Parameter Item No |
Parameter definition |
Adjusting range |
Default value & remark |
|
001 |
Dry run protection trip ampere |
0.0A |
|
|
002 |
Over load protection trip ampere |
26.0A(0.75-7.5KW) 52A(11-15KW) |
|
|
003 |
Pump stalled protection trip ampere |
33.1A(0.75-7.5KW) 66.0A(11-15KW) |
|
|
004 |
Under voltage protection trip voltage |
175V - Default (Single Phase) 300V - Default (Three Phase) |
|
|
005 |
Over voltage protection trip voltage |
253V - Default (Single Phase) 439V - Default (Three Phase) |
|
|
006 |
Dry run protection trip response time |
0-254S |
6S - Default Unit is second (S) |
|
007 |
Dry run protection recovery time |
0-254M |
5M - Default Unit is minute (M) |
|
008 |
3 applications if connection with Pure circle timer (Parameter 009-010) |
00-01 |
00 (no) [01 yes] |
|
009 |
Pure timer control Pump running timer setting |
0-254M |
5M - Default Unit is minute (M) Pump running timer vaild only the controller is under the application of pure circle timer control. |
|
010 |
Pure timer control Pump stop timer setting |
0-254M |
5M - Default Unit is minute (M) Pump stop timer vaild only the controller is under the application of pure circle timer control. |
|
011 |
Pump stop timer under manual state |
0-254M |
0M - Default Unit is minute (M) 0M means this stop timer non activated. |
|
012 |
LCD & button operation lock function |
00-01 |
00 - Default 00= LCD & button operation function non activated 01= LCD & button operation function activated |
|
013 |
Open phase protection &phase reverse protection enable and disable |
00-03 |
03- Default 00=Open phase protection&phase reverse protection disable 01=Open phase protection disable,phase reverse protection enable 02=Open phase protection enable ,phase reverse protection disable 03=Open phase protection &phase reverse protection enable |
|
The following parameter items are only visible when the controller is under the application of temperature control by PT100 temperature sensor and PT100 temperature sensor expansion module equipped. |
|||
|
014 |
Pump start temperature |
0-100℃ |
35℃- Default Unit is degree celsius When temperature is below 35℃, pump will start; |
|
015 |
Pump stop temperature |
0-100℃ |
45℃- Default Unit is degree celsius When temperature is below 45℃, pump will stop; |

Hot Tags: single pump control and protection module., China single pump control and protection module. manufacturers, suppliers, factory, Subersible Three Phase Pump Control Box, Single Phase Motor Protector, Pump Controller, Sewer Control Panel, Duplex Pump Control System, 3 Phase Well Pump Control Box