An intuitive, programmable control and protection system for centrifugal, pipeline, duplex, and three-phase deep well submersible pumps, among other types, is the Intelligent Pump Controller.
The controller can operate in multiple ways by utilizing various electrical installations. The probe or sensor free in the well is a key characteristic that sets the controller apart from a standard On/Off pump control box. Our unique design eliminates the need for an installation probe or sensor in the well and provides a highly sensitive and dependable protection against pump dry run.
Brand: OEM
Manufacturer Model no:PCH32 PLUS
Working in :3 Phase 220v/380v/415v
Working pump :0.75-15kw
Plastic enclosure:IP 65
MCB/AC Contactor:CHNT
Type:Duplex Alternating Control Panel
Rated Voltage:120/208/240V/380V/415V AC
Amps:9 to 32 A
Compatible Pump Type:Sump/booster/borehole pump
Number of Pumps Controlled:2
Location:Indoor/Outdoor
Enclosure Type :IP65
Enclosure size:342*292*119mm

Application shifting :by Dip switch
Application including:
- Applied for water transfer from low tank to upper tank by liquid probe or float switch
- Applied for booster by pressure switch &pressure tank.
- Applied for sewage lifting by liquid probe or float switch
- Applied for drainage pump with piggy-back float switch
- Applied for water transfer from low tank to upper tank by level transmitter(4-20mA)
- Applied for booster by pressure transmitter(4-20mA)
- Applied for sewage lifting by level transmitter(4-20mA)

Protection
| Item | Protection | Value | Remark | Fault type |
| 1 | Dry Run protection trip ampere | 75% of Calibrated running ampere | In menu setting | Recovery fault |
| 2 | Dry Run protection trip response time | 5s | In menu setting | |
| 3 | Dry Run protection recovery time | 45m | In menu setting | |
| 4 | Over Load protection trip ampere | 130% Calibrated running ampere | In menu setting | Recovery fault |
| 5 | Over Load protection trip respone time | 5S(inverse time ) | fixed in software | |
| 6 | Overload protection recovery time | 4m | In menu setting | |
| 7 | Pump Stalled protection trip ampere | 180% of Calibrated running ampere | In menu setting | Unrecovery fault |
| 8 | Pump Stalled protection trip respone time | 1s | fixed in software | |
| 9 | Under Voltage protection trip voltage | 304v | In menu setting | Recovery fault |
| 10 | Under Voltage protection trip respone time | 6s | fixed in software | |
| 11 | Under Voltage protection recovery time | 4m | In menu setting | |
| 12 | Over Voltage protection trip voltage | 437v | In menu setting | Recovery fault |
| 13 | Over Voltage protection trip respone time | 6s | fixed in software | |
| 14 | Over Voltage protection recovery time | 4m | In menu setting | |
| 15 | Open phase | Unrecovery fault | ||
| 16 | Phase reverse | Unrecovery fault | ||
| 17 | Overflow | Recovery fault | ||
| 18 | Over temp | Recovery fault | ||
| 19 | Water leakage | Unrecovery fault |
benefit
Possessing more than 20 years of expertise in the creation, investigation, and advancement of expert water pump controllers,
The result of our efforts are our sewage lift controllers, the PCH series. It has all the capabilities and attributes our customers need, and with a few simple parameter adjustments, it can almost do the functions of several machines.
Its user-friendly settings substantially lengthen the life of the pump, and its one-button setup functionality effectively preserves the water pump.
Its robust overflow alarm system will notify the client in the event of a rapid increase in water volume by simultaneously activating an external siren and speaker.
It can also precisely manage the start and stop of water pumps by handling both switch and analog inputs.
working logic
1). Normal liquid level in the sump
liquid level reaches Probe 3# (Float Switch A: Up Level ), control box will order single pump to
run;liquid level declines to Probe 2# ( Float Switch A:Down Level), single pump stop running;
Control box will alternate double pumps running automatically when the liquid level varies from
Probe 2# & Probe 3# (Float Switch A: Up level- Down level)
2). Extra flowing in the sump
when single pump is running to drainage, liquid level in the sump still increase to Probe 4#
(Float Switch B: Up Level), control box will order another pump to run simultaneously to
drainage, until liquid level declines to Probe 2# (Float Switch A&B:Down Level), double pumps
will not stop running.
3). Overflow in the sump
when double pumps are running simultaneously, liquid level in the sump still increase to Probe
5#(Float Switch C: Up level), control box will sound warning alarm; When liquid level declines
to Probe 5# (Float Switch C Down Level), control box stop sounding warning alarm
4).Auto Patrol (Anti-rust) function
Under Auto state, if control box inspects double pumps not running for ten days, control device
will order pump A to run for 3 seconds and stop, after 10seconds interval, control device will
order pump B to run for 3 seconds and stop.
Auto Patrol can prevent pump rusty and impeller jammed owing to long time no running
Hot Tags: 2 pump intelligent pump controller, China 2 pump intelligent pump controller manufacturers, suppliers, factory, Single Phase Submersible Control Panel, Control Panel Single Phase Submersible Pump, 3 Phase Well Pump Control Box, Sewer Lift Station Control Panel, Single Phase Motor Protector, Sewage Lift Station Control Panels